About this UPS
- Brand: APC by Schneider Electric
- Product Type: Line-interactive UPS
- Manufacturer Part Number: SMT1500X93
- Input Voltage: 120 V
- Form Factor: Tower
- Backup/Run Time (Half Load): 17 Minute
- Backup/Run Time (Full Load): 5 Minute
- Load Capacity: 1.44 kVA/1 kW
Marketing Information:
Smart-UPSâ„¢ are trusted by millions of IT professionals throughout the world to protect equipment and critical data from costly interruptions by supplying reliable, network-grade power reliably and efficiently. Available in a variety of forms factors and classes (entry level, standard and extended run), there is a model for nearly every application and budget. Standard models are the most popular UPS in the world for business servers, storage and network devices and have long been considered the benchmark for reliability and manageability. Entry level Smart-UPS models are an economical choice for small and medium businesses looking to protect small networking devices, point-of-sale (POS) equipment and entry level servers. The extended run models accept external battery packs for long runtime to power critical servers, security and communication systems through outages that could last hours.
Adaptability | Adjustable voltage sensitivity - Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.
Adjustable voltage-transfer points - Maximizes useful battery life by widening the input voltage window or tightening the output voltage regulation.Availability | Power conditioning - Protects connected loads from surges, spikes, lightning, and other power disturbances.
Intelligent battery management - Maximizes battery performance, life, and reliability through intelligent, precision charging.Boost and Trim Automatic Voltage Regulation (AVR) - Gives higher application availability by correcting low and high voltage conditions without using the battery (not available on all models).
Disconnected battery notification - Warns when a battery is not available to provide backup power.
Automatic self-test - Periodic battery self-test ensures early detection of a battery that needs to be replac
ed.
Automatic restart of loads after UPS shutdown - Automatically starts up the connected equipment upon the return of utility power.
Temperature-compensated battery charging - Prolongs battery life by regulating the charge voltage according to battery temperature.
Manageability | Serial connectivity - Provides management of the UPS via a serial port.
LED status indicators - Quickly understand unit and power status with visual indicators.Audible alarms - Provides notification of changing utility power and UPS conditions.
Network manageable - Provides remote power management of the UPS over the network.
USB connectivity - Provides management of the UPS via a USB port (not available on all models).
| PRODUCT SPECIFICATIONS | |
|---|---|
| Plug/Connector Type | NEMA 5-15P |
| Receptacle Type | NEMA 5-15P |
| Receptacle Detail | 8 x NEMA 5-15R |
| Number of Battery & Surge Outlets | 8 |
| Transfer Time | 10 ms |
| Application/Usage |
|
| Load Capacity (VA) | 1.44 kVA |
| Load Capacity (Watt) | 1 kW |
| Input Voltage | 120 V |
| Input Voltage Range | 82 V AC - 144 V AC |
| Output Voltage | 120 V AC |
| Input Frequency | 60 Hz |
| Output Frequency | 60 Hz |
| Waveform Type | Sine Wave |
| Surge Energy Rating | 693 J |
| Alarm | Alarm |
| Status Indicators |
LED status display:
|
| USB (HID Compliant) Port | Yes |
| Number of Batteries | 1 |
| Battery Chemistry | Lead Acid |
| Backup/Run Time (Full Load) | 5 Minute |
| Backup/Run Time (Half Load) | 17 Minute |
| Battery Life | 5 Year |
| Typical Battery Recharge Time | 3 Hour |
| Maximum Operating Temperature | 104 °F (40 °C) |
| Storage Temperature | -4 °F (-20 °C) - 131 °F (55 °C) |
| Storage Relative Humidity | 0% - 95% |
| Sound Emission (A-Weighted) | 45 dB(A) |
| Thermal Dissipation | 225 BTU/h |
| Height | 8.62" (219 mm) |
| Width | 6.73" (171 mm) |
| Depth | 17.28" (439 mm) |
| Form Factor | Tower |
| Mounting Location | Front |
| Weight (Approximate) | 54.23 lb (24598.31 g) |
| Certifications & Standards | CSA C22.2 No 107.1 |
| Green Premium | Yes |
| Product Take Back Program | No |
| Mercury Free | Yes |
| RoHS Exemption Information | https://download.schneider-electric.com/files?p_enDocType=Declaration+of+Conformity+%28Sustainability%29&p_Doc_Ref=SMT1500X93_ROHS_DECLARATION&p_FileName=SMT1500X93KIT_ROHS_DECLARATION_US.pdf |
| REACH Declaration URL | https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=exportPdfReach&pid=559241381&lang=en-us |
| EU RoHS Declaration URL | https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=559241381&lang=en-us |
| Environmental Profile Availability | https://download.schneider-electric.com/files?p_enDocType=Environmental+Disclosure&p_Doc_Ref=ENVPEP1612029_EN |
| End of Life Manual Availability | https://download.schneider-electric.com/files?p_enDocType=Circularity+Profile&p_Doc_Ref=ENVEOLI1612029_EN |
| REACH free of SVHC | No |
| WEEE Statement | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
| Country of Origin | United States |
| TAA Compliant | Yes |
| Environmentally Friendly | Yes |
| Environmental Compliance | Restriction of Hazardous Substances (RoHS) |
| Limited Warranty | 3 Year |
| Additional Warranty Information | 3 years repair or replace (excluding battery) and 2 years for battery |
Technical specifications
How long it'll keep your equipment up.
Manufacturer-specified runtime at typical loads. Real-world figures depend on battery age, ambient temperature, and load profile.
Estimate based on manufacturer-specified runtime curve. Real-world runtime varies with battery age, ambient temperature, and load profile.
Before you order
How do I know this UPS will run my equipment?
Add up the wattage draw of every device you'll plug in (servers, switches, monitors). The UPS's wattage rating — not VA — is the number that matters. Aim for the UPS to run at 60–70% of capacity at full load: this gives headroom for inrush current and a meaningful runtime margin. Email us your equipment list and we'll size the right UPS within one business hour.
What's covered by the warranty, and how long does it last?
New units carry the full manufacturer warranty registered to you on receipt. The manufacturer handles claims directly via their North American support channel. Refurbished units are covered by our own 1-year UPSPLUSBATTERY warranty handled in-house in Canada.
Can I extend runtime beyond what's shown above?
Many Smart-UPS-class models accept an external battery pack (XBP) connected to the rear battery port. If this UPS shows "Extended Runtime Capable: Yes" in the spec grid above, an XBP is supported. Compatible XBPs and the runtime gain they deliver vary by model — contact us if you don't see the right XBP in our catalogue.