About this UPS
Xtreme Power TXVR-5K isolated power conditioner
TXVR-5K is a 5 kVA / 5 kW tower power conditioner with electronic voltage regulation and a built-in galvanic isolation transformer. It has no batteries and provides no backup runtime.
- Capacity: 5 kVA / 5 kW (unity power factor)
- Regulation: output within ±1% across a −45% to +45% input swing
- Isolation: integrated galvanic isolation transformer, active in normal and bypass operation
- Output: 240/120 VAC or 230/115 VAC, dual voltage
- Surge: ANSI/IEEE C62.41 Category A and B (6 kV)
- Transfer: static switch to isolated bypass on overload or fault; manual maintenance bypass
- Communications: RS-232, USB and EPO; slot for an optional Web/SNMP or relay card
- Battery / runtime: none; upgradeable to a UPS with firmware and external battery cabinets
- Approvals: UL 1778, cUL, FCC Class A, RoHS, TAA compliant
- Form factor: tower
Questions before you buy
How do I know this UPS will run my equipment?
Add up the wattage draw of every device you'll plug in (servers, switches, monitors). The UPS's wattage rating (not VA) is the number that matters. Aim for the UPS to run at 60 to 70% of capacity at full load: this gives headroom for inrush current and a meaningful runtime margin. Email us your equipment list; we'll respond within one business day with sizing guidance.
What's covered by the warranty, and how long does it last?
New units carry the warranty coverage stated by the manufacturer; see the product listing or manufacturer documentation for the applicable terms. Refurbished units are covered by the 1-year UPSPLUSBATTERY warranty handled in Canada.
Can I extend runtime beyond what's shown above?
Many Smart-UPS-class models accept an external battery pack (XBP) connected to the rear battery port. If this UPS shows "Extended Runtime Capable: Yes" in the spec grid above, an XBP is supported. Compatible XBPs and the runtime gain they deliver vary by model; contact us if you don't see the right XBP in our catalogue.