Alpha EBP 1275-48B (032-045-XX) (12 batteries required) Battery
- Voltage
- 12 V
- Capacity
- 90.0 Ah
- Batteries
- 1
Compatible replacement battery kits for Alpha Technologies EBP (Extended Battery Pack) cabinets.
Replacing the whole UPS? Refurbished UPS: load-tested, new batteries, 1-year warranty →
Replacement battery cartridges and modules for Alpha Technologies EBP (Extended Battery Pack) Series, the auxiliary battery cabinets and modular extended-runtime packs paired with Alpha CFR, Pinnacle, and ALI Plus UPS systems. Models supported include EBP 24A, EBP 24C, EBP 24CC, EBP 24N, EBP 48A, EBP 48AC, EBP 48I/A RM, EBP 144A, EBP 144E, EBP 144Y, EBP 217-24N, EBP 217-24CRM, EBP 417-24N, EBP 417-24CRM, EBP 417-48B, EBP 417-48CRM, EBP 1233-144, EBP 1275-48B, EBP 1275-48R plus 032-XXX-XX part-number variants.
EBP packs typically use 12V SLA cells in strings ranging from 24V (2-cell), 48V (4-cell), 144V (12-cell), and 217V (18-cell), or 417V (35-cell) configurations. Always confirm the cell count, voltage, and 032-XXX-XX part number on your existing battery cabinet before ordering, EBP packs are NOT interchangeable across Alpha UPS models. Larger EBP cabinets may require 12 individual batteries per kit.
Recommended swap window: 3-5 years per IEEE 1188 in normal operating conditions; outdoor outside-plant cabinet deployments may run hot/cold cycles that shorten life. For EBP cabinet commissioning, hot-swap battery installation, or runtime testing contact our service partner for Canada-wide service.
The Alpha Technologies EBP (Extended Battery Pack) line adds runtime to Alpha UPS and backup-power systems used in broadband, telecom and traffic applications. Each EBP cabinet is wired as a series string of sealed lead-acid (SLA/AGM/VRLA) blocks. Every block in these kits is 12 volts nominal, but the capacity and the number of batteries per kit differ by model. Depending on the model, the kits here use 18 Ah, 35 Ah or 90 Ah blocks, and some cabinets (for example the EBP 144 models and the EBP 1275-48B / 48R) need a full set of 12 batteries to rebuild the string. Because the capacity varies, we do not list one universal spec for the whole series. Use the product that matches your exact EBP model number, and confirm against the specs shown on each product page.
An EBP cabinet does not use a single large battery. It uses several identical 12 V blocks wired in series (and sometimes in parallel strings) to reach the system's DC bus voltage and the runtime the cabinet is rated for. That is why a kit may call for 12 batteries: all blocks in a string age together and must be replaced as a complete set. Mixing old and new blocks, or mixing capacities, shortens the life of the whole string and can leave the cabinet unable to hold its rated runtime.
Alpha EBP cabinets are identified by a model designation plus a dash/part number such as EBP 417-48B (032-056-31) or EBP 1275-48R (031-041-XX). The model and part number are printed on the cabinet label. Match that exact string to the product title and to the compatible-models field on the product page before ordering. The product grid on this page shows the per-block voltage, capacity (Ah) and the number of batteries required for each kit so you can confirm before you buy.
You have two options when an EBP string reaches end of life. OEM packs are sourced through Alpha Technologies / EnerSys and carry the manufacturer's branding. The batteries sold here are compatible replacements matched on voltage, capacity, terminals and connectors, not OEM-branded units. Choose OEM where a warranty or service contract requires it.
Sealed lead-acid blocks in standby float service typically last 3 to 5 years before capacity drops enough to warrant replacement. Heat is the single biggest factor: as a rule of thumb, every 8 °C of sustained operating temperature above 25 °C roughly halves the service life of an SLA battery. A cabinet running warm in a non-climate-controlled enclosure can wear its batteries out in a fraction of the rated life, so plan replacement intervals around the actual environment, not just the calendar.
EBP cabinets are floor- or rack-mounted extended-battery enclosures wired as series strings carrying high DC voltage. These are not desktop units, and they are not designed to be hot-swapped like a plug-in UPS battery module. Treat every replacement as a planned electrical maintenance task and follow the procedure for your cabinet:
Important: if your site cannot tolerate downtime, do not improvise a live swap on an EBP cabinet. Use a temporary backup source or a qualified power-service technician to maintain protection while the string is de-energized and replaced. Always work to the Alpha service manual for your specific cabinet.
How do I know which kit fits my EBP cabinet?
Read the model and part number from the cabinet label (for example EBP 144E (032-036-XX)) and match it exactly to a product title and its compatible-models field. The grid above lists the voltage, Ah and battery count for each kit.
Why does a kit require 12 batteries?
On the EBP 144 models, twelve 12 V blocks form one series string; on the 48 V EBP 1275-48B / 48R, the twelve blocks form parallel strings of four. Either way the whole set must be replaced together so all blocks age together.
Are these Alpha batteries?
No. They are compatible replacements matched on voltage, capacity, terminals and connectors, not OEM-branded packs.
How long will the new batteries last?
Typically 3 to 5 years in float service. Expect less in warm enclosures, since life roughly halves for every 8 °C above 25 °C.
Can I replace just the one dead block?
No. Replace the entire string at once. A single new block forced into a string of aged blocks will be dragged down and fail early.
Model names and trademarks belong to their respective owners. UPSPLUSBATTERY.ca is not affiliated with, endorsed by, or authorized by the manufacturer. Model numbers are referenced solely to indicate compatibility. The batteries offered here are aftermarket compatible replacements.